Skip to main content

Managing Electrical Risks

Electricity kills silently. De-energise by default; energise only when no other reasonable alternative. RCD + test-and-tag + LOTO are the three controls regulators always check.

Quick Take
  • Electrical work = licensed electrician only (state-issued).
  • Construction sites must comply with AS/NZS 3012 (temporary supplies).
  • Test and tag every 3 months for construction equipment.
  • Portable RCDs: monthly push-button test, quarterly competent-person test.
  • Energised work needs a written permit, two-person rule, arc-rated PPE, insulated tools.
  • Electrical workers and safety observers need annual CPR currency.

1. Who's responsible

PCBU

  • Electrical installation work performed by licensed/registered electrical workers only.
  • Construction PCBUs must comply with AS/NZS 3012:2010 (Construction & demolition site electrical installations).
  • Provide RCDs, test/tag programme, isolation procedures, training.

Officer (s.27)

  • Verify systems exist (test/tag register, RCD log, training records).

Worker (s.28)

  • Use as instructed; report damaged cables, missing tags, exposed conductors.

2. De-energisation principle — first rule

Work on electrical equipment must be de-energised unless one or more genuine exceptions apply.

Exceptions:

  • Necessary for health/safety reasons (e.g. life-support).
  • Equipment must be energised for the work itself (e.g. testing, fault-finding).
  • Required to confirm de-energisation.
  • No reasonable alternative exists.

Convenience or schedule pressure is not an exception.

Test for "dead" before you touch:

  1. Test the tester on a known live source.
  2. Test the target equipment.
  3. Re-test the tester to confirm it's still working.
  4. Assume all exposed conductors are live until proven dead.
  5. Re-test if you leave the work area.

3. RCDs (residual current devices)

![[managing_electrical_risks_img001.jpg|520]] Figure 1 — Switchboard-mounted RCD. Fixed protection upstream of multiple circuits.

![[managing_electrical_risks_img002.jpg|520]] Figure 2 — Portable RCD on a power lead. Required where fixed RCDs aren't practicable, especially for tools used in hostile environments.

Required when equipment is supplied via socket outlet and:

  • Used in hostile / higher-risk environments (wet, dusty, outdoor, vibration, corrosive, heat).
  • Frequently moved or moved between job sites.
  • Used on amusement devices.

Trip ratings

  • Type II — ≤ 30 mA trip, ≤ 300 ms (general use).
  • Type I — ≤ 10 mA trip, ≤ 30 ms (medical / direct patient contact).

Testing schedule (construction)

  • New / on installation — full test by competent person.
  • Monthly — operator pushes the trip-test button.
  • Quarterly (3-monthly) — competent-person verification, recorded.
  • Faulty RCDs — out of service immediately.

4. Test and tag — AS/NZS 3760

EnvironmentCycle
Construction / demolition siteEvery 3 months
Manufacturing, workshop, hire equipmentEvery 6 months
Office / low-riskEvery 12 months (or per AS/NZS 3760)

Inspection checks — visual: cord damage, plug integrity, discoloration (heat/moisture), guards, cooling vents, ratings.

Electrical test — earth continuity + insulation resistance via approved tester.

Tag — durable, non-metallic, non-reusable; tester name, date, next test, outcome.

Records — tagger, date, asset ID, result, next due date — logbook or database.

5. Energised electrical work (when unavoidable)

When no reasonable alternative:

  • Written risk assessment + permit by competent person, retained on site.
  • Two-person rule — competent worker + safety observer (unless testing-only with no serious risk).
  • Safety observer — trained in emergency rescue and resuscitation; assessed within 12 months.
  • Arc-rated PPE — gloves, helmet/face shield, apron, non-conductive footwear matched to fault energy.
  • Insulated tools — rated for voltage; inspected before use.
  • Position & barriers — prevent inadvertent contact; restrict unauthorised access.
  • First aid + electrical fire-fighting equipment accessible; CO₂ / dry-chem extinguisher, never water on energised gear.

6. Lockout-tagout (electrical isolation)

![[managing_electrical_risks_img003.jpg|520]] Figure 3 — Locking off a circuit breaker with a hasp + multiple personal locks. Each worker applies their own; supply can't be re-energised while any lock is in place.

![[managing_electrical_risks_img004.jpg|520]] Figure 4 — Danger tag: identifies who, what, when, why; never to be removed by anyone other than the worker who applied it (or under formal escalation if absent).

Sequence:

  1. Consult workplace manager and notify affected persons.
  2. Identify all supply sources (multiple feeds, generators, solar, UPS, standby).
  3. Isolate — open and secure isolators; rack out / remove breakers where practicable.
  4. Lock at the point of isolation; under control of the worker doing the task.
  5. Tag — danger tag dated, signed, "supply must not be reconnected".
  6. Test — verify de-energised.
  7. Re-test if the worker leaves the area or work pauses.

For multi-person work: each person applies a personal lock; last off removes theirs.

Tags warn. Locks isolate. Tags alone are not isolation.

7. Working near energised parts (overhead, underground)

Overhead lines

  • Risk-assessed before work; minimum safe approach distances per state/territory + standards.
  • Eliminate (de-energise via supply authority) → physical isolation (insulated barriers / Tiger Tails) → exclusion / spotters → admin.
  • No metallic / wire-reinforced ladders near live conductors. Wood or fibreglass only.
  • Trained safety observer where work could intrude into approach distance.

Underground services — see [[excavation_work]]:

  • Dial Before You Dig before any excavation.
  • Pothole if location uncertain.
  • Don't assume an unknown buried cable is dead.

8. Construction-site specific (AS/NZS 3012)

  • Temporary supplies — proper protection and control; portable RCDs on socket outlets.
  • Distribution boards — RCD-protected; weatherproofed; protected against site damage.
  • Cables — supported off the ground where possible; protected from vehicle / plant damage; covered ramps where they cross traffic.
  • Plant earthing — confirmed during install; tested periodically.
  • Test and tag every 3 months (vs 6 / 12 elsewhere).
  • SWMS required for HRCW work near energised installations (see [[general_construction_work]]).

9. Records & training

Records

  • Risk assessments + permits for energised work — keep 28 days post-completion (2 yrs if notifiable incident).
  • SWMS — for duration of work; accessible to all workers.
  • Test/tag log — until next test, removal, or disposal.
  • RCD log — monthly + quarterly tests.
  • Training & licence records — sighted before mobilisation.

Training

  • CPR / first aid annual for electrical workers and safety observers.
  • Induction: safe systems, hazard reporting, emergency procedures.
  • Work-specific: isolation procedures, tool / PPE use, energised-work protocols.
  • Refresher periodic.

10. Common pitfalls / quick wins

Do

  • "Test for dead before you touch" every time. The 3-step tester check has saved lives.
  • Issue personal padlocks; one per worker; document the system.
  • Dial Before You Dig before any excavation, even if you think you know the layout.
  • Buy quality cable reels — heat / cord damage is the #1 fire / shock cause on site.
  • Tag missed-test gear out immediately; don't keep using it "until the next round".

Don't

  • Energise "for convenience" or to skip a short outage. Justify only by genuine necessity.
  • Trust the panel voltmeter alone — verify with a hand-tester.
  • Skip the safety observer because "it's just a quick check".
  • Leave bare wires inside an open distribution board waiting for the sparky next week.
  • Wear metallic watches/jewellery near live work.

11. Cross-references

  • See also: [[managing_risks_of_plant]] (general LOTO / isolation principles), [[excavation_work]] (underground services), [[general_construction_work]] (HRCW + SWMS for energised work)
  • Foundations: [[risk_management_process]]
  • Glossary (RCD, LOTO, AS/NZS 3012): [[glossary_and_key_concepts]]

Source: managing_electrical_risks.md (Safe Work Australia, model Code of Practice, CC-BY-NC 4.0). Last verified against SWA: 2026-04-27.